Product Center
Contact Us
Mobile: Mr. Zhou +86-18900715600
Telephone: +86-731-88238888
Hotline: +86-400 0586 896
Email: hzgc@cshnac.com
Address: No. 609, Lusong Road, Lugu, High-tech Zone, Changsha, Hunan Province, China

Share to
GCR-300 Central Display
Category:
Online Equipment Status Monitoring
Keywords:
Product Details
The GCR-300 central display is a high-performance embedded integrated touch screen based on an advanced Cortex-A8 CPU (600MHz main frequency). It supports wireless 4G, 5G, NB, LoRa or wired Ethernet, fiber optic, and RS485 communication methods and has alarm and early warning functions.
Features
- Wireless or wired communication on-site
- Fiber optic connection to the backend server
- Real-time display of on-site temperature measurement data
- On-site early warning and alarm functions
- 7-inch or 10-inch color screen with touch
Main Technical Indicators Integrated Display Panel
Size |
7 inches or 10 inches |
LCD Screen |
TFT LCD display, LED backlight |
Resolution |
800×480 or 1024×600 |
Power Supply |
DC24V±20% |
Rated Power |
5W |
Serial Port |
rs485×1 |
Wireless |
4G, NB, Lora |
Ethernet |
10/100M adaptive Ethernet |
Software Upgrade Interface |
USB |
Operating Temperature |
-10℃~60℃ |
Operating Humidity |
5%~90% |
Installation Method |
Wall-mounted or embedded in switch cabinet |
Panel Size |
226.5×163mm |
Aperture Size |
215×152mm |
Protection Level |
lp65 |
Color |
Industrial Gray |
Integrated Display with Mounting Box (stainless steel shell, optional) Features:
- Number of temperature measurement points connected: Each integrated display can connect up to 432 temperature measurement points.
- Communication interface: 1 RS485 interface, 1 433M wireless interface, 1 Ethernet interface
- Communication distance: In the same switch room (without wall obstruction), 300m can be effectively received.
- Reception interval time: 1s
- Communication protocol: MODBUS-TCP
- Operating power supply: AC/DC220V
- Power consumption: ≤10W
- Operating temperature: -20℃~85℃
- Event recording: Cyclic recording of alarm events
- Temperature threshold: Each cabinet can individually set alarm and early warning values.
- Electromagnetic compatibility: IEC61000 electrostatic discharge interference resistance ±15KV, electrical fast transient pulse group interference resistance, surge interference resistance 2KV, radiated electromagnetic field interference resistance 80MHZ~2.5MHZ, power frequency magnetic field interference resistance 10V/m